HRSL
+
  • HRSL

HRSL

Heat shrink low voltage accessories
keyword:

heat

shrink

repair

Applications:

Forin sulation on low voltage cable up to 1000V

Detailed Specification Download:

留言
  • Basic Information
  • Technical Parameter
  • Ordering Data
    • Commodity name: HRSL
    • Applications: Forin sulation on low voltage cable up to 1000V

    Heat shrink low voltage accessories

    Shelf life & storage:

    HRSL Heat Shrink Cable Repair Sleeve has long shelf life when stored in a humidity controlled storage(-10℃ to 40℃ and < 75% relative humidity).

     

    Ordering information:

    Standard colors:

    Black.

     

    Features:

    Quick and easy installation

    Covered with thermo paint

    Protection against mechanical stress

    Sleeve and channel can be cuttosuit shorter applications

    Forin sulation on low voltage cable up to 1000V

    Hot melt adhesive for msadurable, moisture resistant seal

    Fit a wider ange of cable sizes

  • Key technical performances:

     

    Properties

    Test Condition and Method

    Requirement

    Bursting Strength 

    Test Temp: 23 ±5℃

    15MPa min. 

    Thermal Ageing

    168 hrs at 150℃±2℃

    13.7MPa min

    Bursting strength

    After free shrinkable

    14MPa min

    Dielectric strength

    Electrode Surface                                                        

    Dia: 6mm

    Wight: 50±2gms

    Voltage steps: 2kV/20sec

    Min 12kV/mm

    Split Resistance

    Temp: 200±2℃

    Test time 23±3℃

    No split

    Propagation

    Carbon Content

    UV Res of Out/layer

    Heating rate: 20℃/min

    Gas flow rate: 300cc/min

    Min 2.6±0.25%

    Cold Crack Resistance

    Test temp ≤ -40℃

    No cracking

    Resistance to aggressive

    media

    Bursting Strength

    Test media: Fuel oil, petroleum

    jelly

    Test temp: 70±2℃

    Min 13.7MPa

    Environmental

    Stress cracking

    10% Igepal Co 630

    solution immersion

    Time 30 days

    Test Temp: 50±3℃

    No cracking

    Temp. indicating

    paint conversion

    Completely conversion

    Completely conversion

    Properties of adhesive

    Adhesive Softening Point

    ASTM E28

    90±10℃

    Peel Strength

    -PE at 23±2℃

    -Pb at 23±2℃

    Min 70N

    Shear Strength

    At 23±2℃

    Copper Mirror test

    Test time: 16hrs

    Test temp: 60±℃

    Min 100N

    Corrosive Effect

    ASTM D 1693

    No effect

  • Selection table:

     

     

    Size (mm)

    As supplied(mm) 

    After recovered(mm) 

    Standard Length 

    D*(mm) 

    W*(Min.) 

    d*(Max.) 

    w*(Min.) 

     L(mm)

    36/10

    38

    0.7

    10

    3.2

    500, 750, 1000, 1500

    55/13

    57

    0.7

    13

    3.2

    500, 750, 1000, 1500

    85/20

    85

    0.7

    20

    3.2

    500, 750, 1000, 1500

    108/27

    110

    0.7

    27

    3.2

    500, 750, 1000, 1500

    136/30

    138

    0.7

    30

    3.2

    500, 750, 1000, 1500

    180/50

    183

    0.7

    50

    3.2

    500, 750, 1000, 1500

     

    *NOTE:

    1. D*= Diameter as supplied 

    2. d* = Diameter after recovered

    3. W*= Thickness of sleeve as supplied

    4. w*= Thickness of sleeve after fully recovered

     

Related products