HCSSJ
+
  • HCSSJ

HCSSJ

For XLPE or EPR insulated, 1 or 3 cores cables up to 40.5kV with Al or Cu conductor
keyword:

cold-shrink

joint

hydrophobicity

Applications:

Applying to cold area, humid area, salt mist area and seriously polluted area. Special outer sheaths are available on request, such as heat shrink tubing, cast resin, armoring tape, etc.

Detailed Specification Download:

留言
  • Basic Information
  • Technical Parameter
  • Ordering Data
    • Commodity name: HCSSJ
    • Applications: Applying to cold area, humid area, salt mist area and seriously polluted area. Special outer sheaths are available on request, such as heat shrink tubing, cast resin, armoring tape, etc.

    For XLPE or EPR insulated, 1 or 3 cores cables up to 40.5kV with Al or Cu conductor

    Shelf life & storage:

    HCSSJ Cold Shrink Joint has long shelf life when stored in a humidity controlled storage(-10℃ to 40℃ and < 75% relative humidity).

     

    Features:

    Safety
    Without using torches or any auxiliary tools.

    Stability
    Cold-shrink joint is designed with geometric stress cone on both sides and Faraday Cage in the middle so that stress cone and insulator always keep the active pressure and steady long-term operation to cable.

    Easy installation
    Pull out the plastic string from silicon rubber parts, the silicon rubber will tightly shrink on the need position, which will reduce installation defects.

    Material performance(LSR)
    Excellent performance in anti-flouring, ageing resistance, hydrophobicity, hydrophobicity transference and cold resistance. 

    Wide usage
    Applying to cold area, humid area, salt mist area and seriously polluted area. Special outer sheaths are available on request, such as heat shrink tubing, cast resin, armoring tape, etc.

    Small size
    Smallish cold-shrink joint can minimize stripping distance effectively.
     

  • Key technical performances:

     

    Standard

    IEC 60502

    Voltage classes

    6/10(12)kV

    8.7/15(17.5)kV

    12/20(24)kV

    18/30(36)kV

    26/35(40.5)kV

    Partial discharge test at ambient temperature 

    10kV, <10pC

    15kV, <10pC

    20kV, <10pC

    30kV, <10pC

    45kV,<10pC

    AC withstand voltage test 

    27kV 5min

    39kV 5min

    54kV 5min

    81kV 5min

    117kV 5min

    Impulse voltage withstand

    ±75kV each polarity 10 times

    ±95kV each polarity 10 times

    ±125kV each polarity 10 times

    ±170kV each polarity 10 times

    ±200kV each polarity 10 times

  • Selection table:

     

    6/10(12)kV

     

    Joint

    Cable Insulation OD(mm)

    Cable Conductor Cross-section(mm²)

    1x1 core 

    HCSSJ-12-7095-1

    16.5mm—19.7mm

    70mm²--95mm²

    HCSSJ-12-1215-1

    19.7mm—23.5mm

    120mm²--150mm²

    HCSSJ-12-1830-1

    22.5mm—31.3mm

    185mm²--300mm²

    HCSSJ-12-4063-1

    28.9mm—38.0mm

    400mm²--630mm²

    1x3 cores 

    HCSSJ-12-7095

    16.5mm—19.7mm

    70mm²--95mm²

    HCSSJ-12-1215

    19.7mm—23.5mm

    120mm²--150mm²

    HCSSJ-12-1830

    22.5mm—31.3mm

    185mm²--300mm²

    HCSSJ-12-4063

    28.9mm—38.0mm

    400mm²--630mm²

     

    8.7/15(17.5)kV

     

    Joint

    Cable Insulation OD(mm)

    Cable Conductor Cross-section(mm²)

    1x1 core 

    HCSSJ-17.5-2550-1

    16.5mm—19.7mm

    25mm²--50mm²

    HCSSJ-17.5-7012-1

    19.7mm—23.5mm

    70mm²--120mm²

    HCSSJ-17.5-1530-1

    22.5mm—31.3mm

    150mm²--300mm²

    HCSSJ-17.5-4050-1

    28.9mm—38.0mm

    400mm²--500mm²

    HCSSJ-17.5-630-1

    38.0m m—44.1mm

    630mm²

    1x3 cores 

     

    HCSSJ-17.5-2550

    16.5mm—19.7mm

    25mm²--50mm²

    HCSSJ-17.5-7012

    19.7mm—23.5mm

    70mm²--120mm²

    HCSSJ-17.5-1530

    22.5mm—31.3mm

    150mm²--300mm²

    HCSSJ-17.5-4050

    28.9mm—38.0mm

    400mm²--500mm²

    HCSSJ-17.5-630

    38.0mm—44.1mm

    630mm²

     

    12/20(24)kV

     

    Indoor Termination

    Outdoor Termination

    Cable Insulation OD(mm)

    Cable Conductor Cross-section(mm²)

    1x1 core 

    HCSIT-24-3550-1  

    HCSOT-24-3550-1

    19.7mm—23.5mm

    35mm²--50mm²

    HCSIT-24-7015-1

    HCSOT-24-7015-1

    22.5mm—31.3mm

    70mm²--150mm²

    HCSIT-24-1840-1

    HCSOT-24-1840-1

    28.9mm—38.0mm

    185mm²--400mm²

    HCSIT-24-5063-1

    HCSOT-24-5063-1

    38.0mm—44.1mm

    500mm²--630mm²

    1x3 cores 

    HCSIT-24-3550  

    HCSOT-24-3550

    19.7mm—23.5mm

    35mm²--50mm²

    HCSIT-24-7015

    HCSOT-24-7015

    22.5mm—31.3mm

    70mm²--150mm²

    HCSIT-24-1840

    HCSOT-24-1840

    28.9mm—38.0mm

    185mm²--400mm²

    HCSIT-24-5063

    HCSOT-24-5063

    38.0mm—44.1mm

    500mm²--630mm²

     

    18/30(36)kV

     

    Joint

    Cable Insulation OD(mm)

    Cable Conductor Cross-section(mm²)

    1x1 core 

    HCSSJ-36-5015-1

    25.9mm—33.9mm

    50mm²--150mm²

    HCSSJ-36-1830-1

    33.7mm—41.3mm

    185mm²--300mm²

    HCSSJ-36-4050-1

    41.3mm—47.0mm

    400mm²--500mm²

    HCSSJ-36-630-1

    47.0mm—53.5mm

    630mm²

    1x3 cores 

    HCSSJ-36-5015

    25.9mm—33.9mm

    50mm²--150mm²

    HCSSJ-36-1830

    33.7mm—41.3mm

    185mm²--300mm²

    HCSSJ-36-4050

    41.3mm—47.0mm

    400mm²--500mm²

    HCSSJ-36-630

    47.0mm—53.5mm

    630mm²

     

    26/35(40.5)kV

     

    Joint

    Cable Insulation OD(mm)

    Cable Conductor Cross-section(mm²)

    1x1 core 

    HCSSJ-40.5-5015-1

    33.7mm—41.6mm

    50mm²--150mm²

    HCSSJ-40.5-1830-1

    41.3mm—47.0mm

    185mm²--300mm²

    HCSSJ-40.5-4063-1

    47.0mm—53.5mm

    400mm²--630mm²

    1x3 cores 

    HCSSJ-40.5-5015

    33.7mm—41.6mm

    50mm²--150mm²

    HCSSJ-40.5-1830

    41.3mm—47.0mm

    185mm²--300mm²

    HCSSJ-40.5-4063

    47.0mm—53.5mm

    400mm²--630mm²

     

    *NOTE:

    1. Cable insulation outer diameter is one of the prerequisite for cable accessories selection.

    2. Above product selection is according to the IEC standard cable.

    3. Above product outer sheath is complete with heat shrinkable tubing.

Related products