HSC-100
Applications:
The specially designed chemical formulation and carefully controlled manufacture technology effectively release the high electrical stress present at insulation screen in termination and joint of power cables from 11kV to 24kV.
Features:
Electric stress relief tubing
|
Application up to 24kV
|
Minimum fully shrink temperature: 120℃
|
北京丝袜按摩
Test Items |
Test Method |
Test Requirements |
Tensile strength |
ASTM D 2671 |
8MPa min. |
Ultimate elongation |
ASTM D 2671 |
200% min. |
Heat shock at 200℃/30min |
ASTM D 2671 |
No cracking, dropping |
Permittivity |
IEC 60250 |
15-35 |
Volume resistivity |
IEC 93 |
1011Ω.cm min. |
ESI 09-13 compliant.
UV resistant.
RoHS compliant.
Ordering Information:
Standard colors:
Black
Special colors:
N/A
Dimensions:
Size |
As Supplied |
After Recovery |
Standard |
(mm) |
(mm) |
(mm) |
length |
|
D* (Min.) |
d*(Max.) |
w(Min.) |
|
26/10 |
26 |
10 |
2.1 |
15m/spool |
or 1.0-1.5m |
30/12 |
30 |
12 |
2.2 |
15m/spool |
or 1.0-1.5m |
35/15 |
35 |
15 |
2.3 |
15m/spool |
or 1.0-1.5m |
40/16 |
40 |
16 |
2.4 |
15m/spool |
or 1.0-1.5m |
47/18 |
47 |
18 |
2.4 |
15m/spool |
or 1.0-1.5m |
55/21 |
55 |
21 |
2.4 |
15m/spool |
or 1.0-1.5m |
65/25 |
65 |
25 |
2.4 |
15m/spool |
or 1.0-1.5m |
75/30 |
75 |
30 |
2.4 |
15m/spool |
or 1.0-1.5m |
D* = Inner diameter as supplied