HCSSJ
Applications:
Cold Shrink Joint for XLPE or EPR insulated, 1 or 3 cores cables up to 40.5kV with Al or Cu conductor
Features:
Stability: Cold-shrink joint is designed with geometric stress cone on both sides and Faraday Cage in the middle so that stress cone and insulator always keep the active pressure and steady long-term operation to cable.
Easy installation: Pull out the plastic string from silicon rubber parts, the silicon rubber will tightly shrink on the need position, which will reduce installation defects.
Material performance(LSR): Excellent performance in anti-flouring, ageing resistance, hydrophobicity, hydrophobicity transference and cold resistance.
北京丝袜按摩
Standard |
IEC 60502 |
Voltage classes |
6/10(12)kV |
8.7/15(17.5)kV |
12/20(24)kV |
18/30(36)kV |
26/35(40.5)kV |
Partial discharge test at ambient temperature |
10kV, <10pC |
15kV, <10pC |
20kV, <10pC |
30kV, <10pC |
45kV, <10pC |
AC withstand voltage test |
27kV 5min |
39kV 5min |
54kV 5min |
81kV 5min |
117kV 5min |
Impulse voltage withstand |
±75kV each polarity 10 times |
±95kV each polarity 10 times |
±125kV each polarity 10 times |
±170kV each polarity 10 times |
±200kV each polarity 10 times |
RoHS compliant.
*NOTE: 1. Cable insulation outer diameter is one of the prerequisite for cable accessories selection
Dimensions:
6/10(12)kV |
Joint |
Cable Insulation OD(mm) |
Cable Conductor Cross-section(mm²) |
1x1 core |
HCSSJ-12-7095-1 |
16.5mm—19.7mm |
70mm²--95mm² |
HCSSJ-12-1215-1 |
19.7mm—23.5mm |
120mm²--150mm² |
HCSSJ-12-1830-1 |
22.5mm—31.3mm |
185mm²--300mm² |
HCSSJ-12-4063-1 |
28.9mm—38.0mm |
400mm²--630mm² |
1x3 cores |
HCSSJ-12-7095 |
16.5mm—19.7mm |
70mm²--95mm² |
HCSSJ-12-1215 |
19.7mm—23.5mm |
120mm²--150mm² |
HCSSJ-12-1830 |
22.5mm—31.3mm |
185mm²--300mm² |
HCSSJ-12-4063 |
28.9mm—38.0mm |
400mm²--630mm² |
8.7/15(17.5)kV |
Joint |
Cable Insulation OD(mm) |
Cable Conductor Cross-section(mm²) |
1x1 core |
HCSSJ-17.5-2550-1 |
16.5mm—19.7mm |
25mm²--50mm² |
HCSSJ-17.5-7012-1 |
19.7mm—23.5mm |
70mm²--120mm² |
HCSSJ-17.5-1530-1 |
22.5mm—31.3mm |
150mm²--300mm² |
HCSSJ-17.5-4050-1 |
28.9mm—38.0mm |
400mm²--500mm² |
HCSSJ-17.5-630-1 |
38.0m m—44.1mm |
630mm² |
1x3 cores |
|
HCSSJ-17.5-2550 |
16.5mm—19.7mm |
25mm²--50mm² |
HCSSJ-17.5-7012 |
19.7mm—23.5mm |
70mm²--120mm² |
HCSSJ-17.5-1530 |
22.5mm—31.3mm |
150mm²--300mm² |
HCSSJ-17.5-4050 |
28.9mm—38.0mm |
400mm²--500mm² |
HCSSJ-17.5-630 |
38.0mm—44.1mm |
630mm² |
12/20(24)kV |
Joint |
Cable Insulation OD(mm) |
Cable Conductor Cross-section(mm²) |
1x1 core |
HCSSJ-24-3550-1 |
19.7mm—23.5mm |
35mm²--50mm² |
HCSSJ-24-7015-1 |
22.5mm—31.3mm |
70mm²--150mm² |
HCSSJ-24-1840-1 |
28.9mm—38.0mm |
185mm²--400mm² |
HCSSJ-24-5063-1 |
38.0mm—44.1mm |
500mm²--630mm² |
1x3 cores |
HCSSJ-24-3550 |
19.7mm—23.5mm |
35mm²--50mm² |
HCSSJ-24-7015 |
22.5mm—31.3mm |
70mm²--150mm² |
HCSSJ-24-1840 |
28.9mm—38.0mm |
185mm²--400mm² |
HCSSJ-24-5063 |
38.0mm—44.1mm |
500mm²--630mm² |
18/30(36)kV |
Joint |
Cable Insulation OD(mm) |
Cable Conductor Cross-section(mm²) |
1x1 core |
HCSSJ-36-5015-1 |
25.9mm—33.9mm |
50mm²--150mm² |
HCSSJ-36-1830-1 |
33.7mm—41.3mm |
185mm²--300mm² |
HCSSJ-36-4050-1 |
41.3mm—47.0mm |
400mm²--500mm² |
HCSSJ-36-630-1 |
47.0mm—53.5mm |
630mm² |
1x3 cores |
HCSSJ-36-5015 |
25.9mm—33.9mm |
50mm²--150mm² |
HCSSJ-36-1830 |
33.7mm—41.3mm |
185mm²--300mm² |
HCSSJ-36-4050 |
41.3mm—47.0mm |
400mm²--500mm² |
HCSSJ-36-630 |
47.0mm—53.5mm |
630mm² |
26/35(40.5)kV |
Joint |
Cable Insulation OD(mm) |
Cable Conductor Cross-section(mm²) |
1x1 core |
HCSSJ-40.5-5015-1 |
33.7mm—41.6mm |
50mm²--150mm² |
HCSSJ-40.5-1830-1 |
41.3mm—47.0mm |
185mm²--300mm² |
HCSSJ-40.5-4063-1 |
47.0mm—53.5mm |
400mm²--630mm² |
1x3 cores |
HCSSJ-40.5-5015 |
33.7mm—41.6mm |
50mm²--150mm² |
HCSSJ-40.5-1830 |
41.3mm—47.0mm |
185mm²--300mm² |
HCSSJ-40.5-4063 |
47.0mm—53.5mm |
400mm²--630mm² |
2. Above product selection is according to the IEC standard cable.
3. Above product outer sheath is complete with heat shrinkable tubing.