HAT/HATA
Applications:
Used to provide insulation protection for cable terminal, load-break switches, power circuit breakers, etc.
Features:
Anti-tracking
Flame retardant
3:1 Shrink ratio allows a few sizes to cover a wide range of applications
Application up to 36kV
UV and weather resistant
Flexible and able to conform to irregular shapes
Min. full recovery temp.: 120℃
北京丝袜按摩
Test Items |
Test Method |
Test Requirements |
Tensile strength |
ASTM D 2671 |
10MPa min. |
Ultimate elongation |
ASTM D 2671 |
200% min. |
Tensile strength after |
ASTM D 2671 |
10MPa min. |
Aging at 150℃ for 168hrs |
Ultimate elongation after |
ASTM D 2671 |
100% min. |
Aging at 150℃ for 168hrs |
Heat shock at 200℃/30min |
ASTM D 2671 |
No cracking, dropping |
Density |
ASTM D 792 |
1.2~1.3g/cm3 |
Dielectric strength |
IEC 60243 |
10kV/mm(2.5mm) min. |
Volume resistivity |
ASTM D 2671 |
1012Ω.cm min. |
Low temperature flexibility |
ASTM D 2671 Proc.C |
No cracking |
-40℃/4hrs |
Permittivity |
ASTM D 150 |
3 (nom.) |
Tracking resistance |
ASTM D 2303 |
No tracking |
RoHS compliant.
Ordering Information:
Standard colors:
Red
Special colors:
N/A
Dimensions:
Continues length tubing (HAT) |
Size |
As supplied |
After recovered |
Standard length |
Size |
As supplied |
After recovered |
Standard length |
(mm) |
(mm) |
(mm) |
(mm) |
(mm) |
(mm) |
|
D*(Min.) |
d*(Max.) |
w(Min.) |
|
D*(Min.) |
d*(Max.) |
w(Min.) |
|
|
19/6 |
19 |
6 |
2.5 |
30m/spool or 0.5-1.5m |
65/21 |
65 |
21 |
3.3 |
30m/spool or 0.5-1.5m |
30/10 |
30 |
10 |
2.9 |
30m/spool or 0.5-1.5m |
75/25 |
75 |
25 |
3.5 |
30m/spool or 0.5-1.5m |
Dec-38 |
38 |
12 |
2.9 |
30m/spool or 0.5-1.5m |
85/29 |
85 |
29 |
3.5 |
30m/spool or 0.5-1.5m |
40/16 |
40 |
16 |
2.9 |
30m/spool or 0.5-1.5m |
100/40 |
100 |
40 |
4 |
30m/spool or 0.5-1.5m |
49/16 |
49 |
16 |
2.9 |
30m/spool or 0.5-1.5m |
130/50 |
130 |
50 |
4 |
1.0-1.5m |
55/18 |
55 |
18 |
2.9 |
30m/spool or 0.5-1.5m |
|
|
|
|
|
Cut length tubing (HATA) |
Size |
As supplied |
After recovered |
Standard length |
Size |
As supplied |
After recovered |
Standard length |
(mm) |
(mm) |
(mm) |
(m) |
(mm) |
(mm) |
(mm) |
(m) |
|
D*(Min.) |
d*(Max.) |
w(Min.) |
|
|
D*(Min.) |
d*(Max.) |
w(Min.) |
|
|
|
|
|
30/10 |
30 |
10 |
2.9 |
1.0-1.5 |
65/21 |
65 |
21 |
3.3 |
1.0-1.5 |
40/12 |
40 |
12 |
2.9 |
1.0-1.5 |
75/25 |
75 |
25 |
3.5 |
1.0-1.5 |
43/14 |
43 |
14 |
2.9 |
1.0-1.5 |
85/29 |
85 |
29 |
3.5 |
1.0-1.5 |
49/16 |
49 |
16 |
2.9 |
1.0-1.5 |
100/40 |
100 |
40 |
4 |
1.0-1.5 |
55/18 |
55 |
18 |
2.9 |
1.0-1.5 |
130/50 |
130 |
50 |
4 |
1.0-1.5 |
D* = Inner diameter as supplied
d* = Inner diameter after fully recovered