HKSJ
Applications:
Heat Shrink Joint for XLPE or EPR insulated, 1 or 3 cores cables up to 36kV
Features:
High mechanical strength
Wide cross section range suitable for all types of connectors
Compact dimensions
Weathering stability
Allows immediate reenergizing
Passed type test according to CENELEC HD 629.1 S2 & IEC 60502 in KEMA.
北京丝袜按摩
Standard |
IEC 60502 |
Voltage classes |
6/10(12)kV |
8.7/15(17.5)kV |
12/20(24)kV |
18/30(36)kV |
Partial discharge test at ambient temperature |
10kV, <10pC |
15kV, <10pC |
20kV, <10pC |
30kV, <10pC |
AC withstand voltage test |
27kV 5min |
39kV 5min |
54kV 5min |
81kV 5min |
Impulse voltage withstand |
±75kV each polarity 10 times |
±95kV each polarity 10 times |
±125kV each polarity 10 times |
±170kV each polarity 10 times |
RoHS compliant.
Dimensions:
6/10(12)kV |
Joint |
Cable Insulation OD(mm) |
Cable Conductor Cross-section(mm²) |
1x1 core |
HKSJ-12/1×25-50 |
12.0mm-16.0mm |
25mm²--50mm² |
HKSJ-12/1×70-150 |
17.6mm-22.8mm |
70-mm²--150mm² |
HKSJ-12/1×185-300 |
24.0mm-31.0mm |
185mm²--300mm² |
HKSJ-12/1×400-500 |
31.5mm-37.0mm |
400mm²--500mm² |
HKSJ-12/1×630 |
38.0mm-41.9mm |
630mm² |
1x3 cores |
HKSJ-12/3×25-50 |
12.0mm-16.0mm |
25mm²--50mm² |
HKSJ-12/3×70-150 |
17.6mm-22.8mm |
70-mm²--150mm² |
HKSJ-12/3×185-300 |
24.0mm-31.0mm |
185mm²--300mm² |
HKSJ-12/3×400-500 |
31.5mm-37.0mm |
400mm²--500mm² |
8.7/15(17.5)kV |
Joint |
Cable Insulation OD(mm) |
Cable Conductor Cross-section(mm²) |
1x1 core |
HKSJ-17.5/1×25-50 |
16.0mm-19.5mm |
25mm²--50mm² |
HKSJ-17.5/1×70-150 |
20.3mm-23.5mm |
70-mm²--150mm² |
HKSJ-17.5/1×185-300 |
24.0mm-31.0mm |
185mm²--300mm² |
HKSJ-17.5/1×400-500 |
31.5mm-37.0mm |
400mm²--500mm² |
HKSJ-17.5/1×630 |
38.0mm-41.9mm |
630mm² |
1x3 cores |
HKSJ-17.5/3×25-50 |
16.0mm-19.5mm |
25mm²--50mm² |
HKSJ-17.5/3×70-150 |
20.3mm-23.5mm |
70-mm²--150mm² |
HKSJ-17.5/3×185-300 |
24.0mm-31.0mm |
185mm²--300mm² |
HKSJ-17.5/3×400-500 |
31.5mm-37.0mm |
400mm²--500mm² |
12/20(24)kV |
Joint |
Cable Insulation OD(mm) |
Cable Conductor Cross-section(mm²) |
1x1 core |
HKSJ-24/1×25-50 |
17.5mm-20.3mm |
25mm²--50mm² |
HKSJ-24/1×70-150 |
21.5mm-26.5mm |
70-mm²--150mm² |
HKSJ-24/1×185-300 |
27.5mm-33.0mm |
185mm²--300mm² |
HKSJ-24/1×400-500 |
34.2mm-39.5mm |
400mm²--500mm² |
HKSJ-24/1×630 |
40.5mm-43.0mm |
630mm² |
1x3 cores |
HKSJ-24/3×25-50 |
17.5mm-20.3mm |
25mm²--50mm² |
HKSJ-24/3×70-150 |
21.5mm-26.5mm |
70-mm²--150mm² |
HKSJ-24/3×185-300 |
27.5mm-32.8mm |
185mm²--300mm² |
HKSJ-24/3×400-500 |
33.5mm-39.5mm |
400mm²--500mm² |
18/30(36)kV |
Joint |
Cable Insulation OD(mm) |
Cable Conductor Cross-section(mm²) |
1x1 core |
HKSJ-36/1×50-95 |
25.0mm-29.5mm |
50mm²--95mm² |
HKSJ-36/1×120-240 |
30.5mm—36.5mm |
120mm²--240mm² |
HKSJ-36/1×300-400 |
38.0mm-42.5mm |
300mm2--400mm² |
HKSJ-36/1×500-630 |
43.5mm-48.5mm |
500mm2--630mm² |
1x3 cores |
|
|
HKSJ-36/3×50-95 |
25.0mm-29.5mm |
50mm²--95mm² |
HKSJ-36/3×120-240 |
30.5mm—36.5mm |
120mm²--240mm² |
HKSJ-36/3×300-400 |
38.0mm-42.5mm |
300mm2--400mm² |
*NOTE: 1. Cable insulation outer diameter is one of the prerequisite for cable accessories selection.
2. Above product selection is according to the IEC standard cable.