HTRT
Applications:
The tubing manufactured with special technology, is very suitable for applications in power cable joints up to 36kV.
Features:
Semi conductive/insulation/elastomer triple layer
Application up to 36kV
Min.full recovery temp.: 130℃
北京丝袜按摩
Test Items |
Test Method |
Test Requirements |
Insulation layer |
|
|
Tensile strength |
ASTM D 2671 |
10MPa min. |
Ultimate elongation |
ASTM D 2671 |
200% min. |
Volume resistivity |
IEC 93 |
1014Ω.cm max. |
Water absorption |
ISO 62 |
0.5% max. |
Elastomer layer |
|
|
Tensile strength |
ASTM D 2671 |
5MPa min. |
Ultimate elongation |
ASTM D 2671 |
500% min. |
Volume resistivity |
IEC 93 |
1014Ω.cm min. |
Semi conductive layer |
|
|
Tensile strength |
ASTM D 2671 |
12MPa min. |
Ultimate elongation |
ASTM D 2671 |
200% min. |
Volume resistivity |
ASTM D 257 |
104Ω.cm max. |
RoHS compliant.
Ordering Information:
Standard colors:
Black/Red
Special colors:
N/A
Dimensions:
Size (mm) |
As supplied (mm) |
After recovered (mm) |
|
Standard Length (m) |
|
D*(Min.) |
d*(Max.) |
w(Min.) |
|
13485 |
36 |
12 |
7.3 |
1.0-1.22 |
46/15 |
46 |
15 |
7.3 |
1.0-1.22 |
50/18 |
50 |
18 |
7.3 |
1.0-1.22 |
56/21 |
56 |
21 |
7.3 |
1.0-1.22 |
62/25 |
62 |
25 |
7.3 |
1.0-1.22 |
70/30 |
70 |
30 |
7.3 |
1.0-1.22 |
80/36 |
80 |
36 |
7.3 |
1.0-1.22 |
95/40 |
95 |
40 |
7.3 |
1.0-1.22 |
120/50 |
120 |
50 |
7.3 |
1.0-1.22 |
D* = Inner diameter as supplied
d* = Inner diameter after fully recovered